PE Power Sample Problem 4

A 3-phase, 15kV/5kV, 𝛥-Y, 60Hz, 10MVA power distribution transformer has 5% per-unit leakage reactance and negligible resistance. The actual transformer impedance based on the ratings on its high voltage side is ____.
(A) 22.5Ω
(B) 2.5Ω
(C) 1.125Ω
(D) 0.125Ω